Martin Cook Electrical carried out an EICR to a large commercial premises in October 2020, and it was highlighted within the observations that there was a fuse that was overheating, and was too rigid to pull out from the fuse carrier. We recommended that the fuse carrier and fuse was investigated further.
Once we obtained permission from the client, the building was shut down and our engineers identified what the issue was within the fuse carrier. There was signs of overheating from lack of maintenance and a lose connection at the rear of the fuse carrier.. We replaced the fuse and fuse carrier and tightened all connections with a torque wrench to the manufacturers specification. We tested the circuit to ensure the circuit was safe for continued use. Our Remedial completion sheet was sent to the client along with a Minor Works Certificate.